VRF capacity estimate
Enter your rooms; see the indoor unit size per room, the total load, the outdoor unit size and the connection ratio.
Total load, connected capacity and the outdoor unit
Room load: area × unit load for the use × region × sun factor. Example: a 40 m² office in Marmara with average sun is 40 × 115 W/m² ≈ 4.6 kW; the next indoor unit size up is 5.6 kW.
Connected capacity: the nominal total of the selected indoor units. It exceeds the total load because sizes are rounded up.
Outdoor unit: the smallest size that covers total load × diversity while keeping the connection ratio under 130%. A very low ratio means the outdoor unit is oversized; a very high one means indoor units can't all run at full capacity together.
Fresh air loads, glazing ratios, internal heat gains, pipe length and height-difference capacity corrections, heating capacity checks and brand selection tables are not included. Final selection is made with the site survey and design calculation.